Product Overview
| Feature | Specification |
| Standard | UL 3644 |
| Insulation Material | Silicone Rubber (High Flexibility) |
| Rated Voltage | 1000V AC |
| Temperature Range | -60°C to +150°C / 200°C (-76°F to +302°F / 392°F) |
| Conductor Type | Tinned Copper (TC) or Nickel-plated Copper (NPC) |
| Available Colors | White, Blue, Red, Black, Brown, Yellow, Green, Transparent, Yellow/Green |
| Applications | Internal wiring of appliances, New Energy systems, Energy Storage System (ESS) battery leads. |
Technical Parameter Table
| AWG (Gauge) | Conductor Construction (No./mm) | Conductor Diameter (mm) | Insulation Thickness (mm) | Overall Diameter (O.D.) (mm) | Max. Conductor Resistance @ 20°C (68°F) (Ohm/km) |
| 18 | 7 / 0.40 | 1.2 | 0.76 | 2.75 | 23.2 |
| 16 | 7 / 0.50 | 1.55 | 0.76 | 3.1 | 14.6 |
| 14 | 41 / 0.254 | 1.95 | 0.76 | 3.5 | 8.96 |
| 12 | 65 / 0.254 | 2.5 | 0.76 | 4.05 | 5.64 |
| 10 | 75 / 0.30 | 3.2 | 0.76 | 4.75 | 3.55 |
| 8 | 119 / 0.30 | 4.4 | 1.14 | 6.75 | 2.3 |
| 6 | 106 / 0.40 | 5.3 | 1.52 | 8.4 | 1.42 |
| 5 | 133 / 0.40 | 6.0 | 1.52 | 9.1 | 1.12 |
| 4 | 168 / 0.40 | 6.8 | 1.52 | 9.9 | 0.89 |
| 3 | 213 / 0.40 | 7.6 | 1.52 | 10.7 | 0.707 |
| 2 | 268 / 0.40 | 8.5 | 1.52 | 11.6 | 0.56 |
| 1 | 338 / 0.40 | 9.6 | 2.03 | 13.7 | 0.449 |
| 1/0 | 665 / 0.32 | 11.2 | 2.03 | 15.4 | 0.355 |
| 2/0 | 538 / 0.40 | 12.2 | 2.03 | 16.4 | 0.282 |
| 3/0 | 677 / 0.40 | 13.8 | 2.03 | 18.0 | 0.223 |
| 4/0 | 854 / 0.40 | 15.5 | 2.03 | 19.7 | 0.177 |
Professional Industry Terminology
-
Silicone Rubber Insulation: Provides excellent thermal stability and remains flexible at cryogenic temperatures down to -60°C (-76°F). It is highly resistant to UV, ozone, and harsh environmental aging.
-
High-Flexibility Stranding: The conductor uses multiple fine strands of tinned copper to ensure maximum bend radius performance, making it ideal for the complex routing required in energy storage cabinets.
-
Tinned Copper (TC): Offers superior conductivity while adding a protective layer against corrosion and oxidation, especially important for high-humidity battery environments.
-
1000V AC Rating: Specifically engineered for high-voltage energy storage systems where standard 600V cables may not provide sufficient safety margins.
-
Flame Retardancy: Complies with horizontal and vertical flame tests, ensuring safety in critical infrastructure applications.